Specifications︰
Installation Instructions
1. Vertically mounted only.
2. Install as close to the compressor as possible.
3. Suction line from evaporator into inlet connection installed to suction line of compressor.
4. Reverse cycle systems required. Accumulator to be installed between the compressor and the reversing valve.
5. Keep direct flame away from fusible relief device while soldering connections.
6. Safe working pressure 450 PSI.
Maximum recommended actual tons based on pressure drop through accumulator equivalent to 1/2*F.
Minimum recommended tons based on minimum flow through accumulator necessary to insure positive oil return.
All data is based on actual tons and bears no relationship to horsepower.
Minimum evaporator temperature -40*F. Minimum suction gas temperature through accumulator +10*F.
Item No. RA-204 : Size Conn. ODF 1/2 , Length 8" x Dia. 4".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 3.5 , R-22 : 3.3
R-502 : 3.4 .
Item No. RA-205 : Size Conn. ODF 5/8 , Length 10-5/8" x Dia. 4".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 4.4 , R-22 : 4.0
R-502 : 4.2 .
Item No. RA-206 : Size Conn. ODF 3/4 , Length 9" x Dia. 5-1/2".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 6.1 , R-22 : 6.8
R-502 : 6.2 .
Item No. RA-207 : Size Conn. ODF 7/8 , Length 12" x Dia. 5-1/2".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 9.8 , R-22 : 9.0
R-502 : 9.3 .
Item No. RA-208 : Size Conn. ODF 1-1/8 , Length 15" x Dia. 6-1/2".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 14.2 , R-22 :
13.3 , R-502 : 13.7 .
Item No. RA-209 : Size Conn. ODF 1-3/8 , Length 20" x Dia. 6-1/2".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 21.8 , R-22 :
20.5 , R-502 : 21.2 .
Item No. RA-210 : Size Conn. ODF 1-5/8 , Length 22" x Dia. 6-1/2".
Refrigerant Holding Cap ( Lbs 0*F sat ) : R-12 : 23.8 , R-22 :
22.6 , R-502 : 23.1 .